Hydrant Pillar & Outdoor Hidrant Box
Before we design we must first determine the needs of the unit fire hydrant in the area that we will design. in this case we determine the location of the hydrant with one another is based on the hydrant hose range is 30 m.
Example :
Note :
Hydrant Pillar 10 Units
Cover area 45 m
Flow rate 80 gpm
working pressure 10 kg/cm2
2. Pump capacity
80 gpm x 10 = 800 gpm
Area fire 30% of the buildings on the layout, the figure of 30% is very useful to determine the capacity of the pump
800 gpm x 30% = 240 gpm
After a known requirement is 240 GPM pump, now we have to look at the table to determine the pump.
Pump Curve |
Seen from the table above, we get a kind of pump that is:
Capacity = 250 gpm
Head = 140 Meters
Rotary = 3000 rpm
2. Calculate Pipe For Fire Fighting
For more table Click Here
To calculate the diameter that will be installed, we have to calculate the start of the end of the water demand.
if the needs of each fire fighting is 80 gpm. Based on the table above, then we will get the size of the pipe with a diameter of 2 1/2 Inch.
Or you can use a calculator pipe following :
if the needs of each fire fighting is 80 gpm. Based on the table above, then we will get the size of the pipe with a diameter of 2 1/2 Inch.
Or you can use a calculator pipe following :
Now we've got the size of the end of the pipe that will be installed.
after that we add the required amount of water based on the amount of fire fighting to determine the size of the next pipe, and continue to add up until the end of the pump.
Note:
Keep in mind!!!!! ... Operator may not use the fire fighting them simultaneously.
for that you should be able to assume how many meters each operator will be using, so that you can determine the proper pipe size requirements.
Suppose there are 15 in the area of fire fighting, probably in use only 5 or 6 that simultaneously. so the size of the pipe is calculated up to the end of the pump may be sized for 5 to 6 fire fighting.
Calculation of pipe are finished,,
How??
Easy right??
3.Pump Room Instalation
Fire Pump Package
a. Diesel Fire Pump
function:
As a backup fire pump if electrical power is not available anymore for extinguishing operation.
Powered by Diesel Engine
Start operation automatically based pressure sensors (pressure switch)
Stop operation manually based pressure sensors (pressure switch) AND the Stop button.
b. Electric Fire Pump
function:
As the main fire pump.
If the sprinkler breaks or Hydrant Pillar opened for extinguishing the fire, the electric pump will operate automatically.
operation:
Driven by electric motor
Start operation automatically based pressure sensors (pressure switch)
Stop operation manually based pressure sensors (pressure switch) AND stop button.
c. Jockey Fire Pump
function:
Keeping the pressure in the pipeline remains in standby
If there is a small leak in the pipeline, it will operate Jockey Pump (automatically) to restore pressure in the network.
operation:
Driven by electric motor
Start & Stop operation automatically based pressure sensors (pressure switch)
d. Hydrant Box Detail
Hydrant Box Detail
Posted by 8:43 PM
, Published at
terimakasih informasinya bro. Sangat bermanfaat.
ReplyDeletesama samaaaa
DeletePak bisa minta gambar2 instalasi dari pump hingga hydrant pilar, apa saja yang dibutuhkannya. Terima kasiah
Deletealisobirinm@gmail.com
We essa techFire Hydrant System comprises of AC motor driven pump sets with all required accessories, including valves, instrumentation and controls. In a critical fire wet riser or the down comer which is connected to fire hydrant system plays a major role in ejecting water or the foam to control fire accidents.
ReplyDeleteWe essa techFire Hydrant System comprises of AC motor driven pump sets with all required accessories, including valves, instrumentation and controls. In a critical fire wet riser or the down comer which is connected to fire hydrant system plays a major role in ejecting water or the foam to control fire accidents.
ReplyDeleteThis comment has been removed by the author.
ReplyDeleteGreat information you have explained about fire hydrant system
ReplyDeleteTerima kasih atas informasinya, saya mau menanggapi tentang dasar perhitungan diatas dari mana ya? Karena minimum flow hydrant valve adalah 250 gpm dg pressure min 6.9 bar.
ReplyDeletePak bisa minta gambar2 instalasi dari pump hingga hydrant pilar, apa saja yang dibutuhkannya. Terima kasiah
Deletealisobirinm@gmail.com
This comment has been removed by the author.
ReplyDelete“Thanks for posting this blog is quite informative and helpful. For more information in regards to Fire Hydrant Systems do visit our website.”
ReplyDeletewhat is this 80 GPm and 45 m coverage
ReplyDeleteThanks For sharing very helpful information
ReplyDeleteFire Hydrant System
Hi there! great post. Thanks for sharing some very interesting and informative content it is a big help to me as well, keep it up!!!
ReplyDeleteFire Hydrant system Installation in Chennai
nice post..
ReplyDeleteFire Extinguisher in Chennai
Fire Extinguisher In OMR
Nice Blog Comment...
ReplyDeleteFire Extinguisher, Hydrant Systems Dealers
Fire Extinguisher Dealers in Chennai
Fire Extinguisher Refilling in Chennai